Braced Post Insulators
+
  • Braced Post Insulators

Braced Post Insulators

Category:

Transmission


Application Scope:Transmission

Standards & Compliance:Post component complies with ANSI/NEMA C29.17-2022 and IEC 61952:2008; brace component complies with ANSI/NEMA C29.12-2020 and IEC 61109:2008

Product Overview:Assembly consisting of a line post and a suspension insulator, forming a triangular brace to deliver enhanced cantilever strength for angle towers and dead-end positions. Ideal for applications demanding higher mechanical capacity than standard line posts.

Keywords:

Braced Post Insulators

Description

Key Features & Advantages:

  • Triangular support structure significantly boosts load capacity
  • Field-adjustable brace angle (30°-45°) to fit various tower geometries
  • Suitable for angle and dead-end towers
  • Customizable assemblies with diverse brace lengths and hardware finishes

 

Core Parameters

Catalog

 No.

Voltage Rating

 (kV)

Post Section Length

 (mm/in)

Brace Section Length

 (mm/in)

SCL

 (kN/kip)

Max. Vertical Load

 (kN/kip)

Dry Flashover

 (kV)

Wet Flashover

 (kV)

Impulse Pos. 

(kV)

Impulse Neg.

 (kV)

BLP-920-100069920 / 36.21000 / 39.427 / 6.148 / 10.8280255430540
BLP-1150-12201151150 / 45.31220 / 48.038 / 8.560 / 13.5385320605635
BLP-1460-14801381460 / 57.51480 / 58.344 / 9.968 / 15.3485425735840
BLP-1550-16001611550 / 61.01600 / 63.048 / 10.872 / 16.2515450770880
BLP-2450-27002302450 / 96.52700 / 106.352 / 11.778 / 17.586079013501440
BLP-2750-29503452750 / 108.32950 / 116.150 / 11.275 / 16.9106095016801770

Note: System cantilever loads are typical values based on combined rating. Contact TIMPOWER for application-specific ratings.