Deadend Composite Insulators
+
  • Deadend Composite Insulators

Deadend Composite Insulators

Category:

Distribution


Application Scope:Distribution

Standards & Compliance:Complies with ANSI/NEMA C29.13-2018 and IEC 61109:2008

Product Overview:Insulators designed for distribution line termination, angle poles and tap connections. Capable of withstanding full conductor tension.

Keywords:

Deadend Composite Insulators

composite insulators

Description

Key Features:

  • Rated Tensile Load (RTL): 66.5 kN / 15,000 lbs (95% SML)
  • Triple-sealed end fittings
  • UV-stabilized silicone housing
  • Ball & socket, eye, or clevis fittings available

 

Core Parameters

Catalog

 No.

Voltage Rating

 (kV)

Section Length

 (mm/in)

Leakage Distance

 (mm/in)

SML

 (kN/kip)

Dry Flashover

 (kV)

Wet Flashover

 (kV)

Impulse Pos.

 (kV)

Impulse Neg. 

(kV)

Min.Torsional Load

 (Nm/ft-lbs)

DS-15-33015330 / 13.6420 / 16.570 / 15.0956514014650 / 36.9
DS-28-43028430 / 17.0595 / 23.470 / 15.013010019020050 / 36.9
DS-35-52535525 / 20.6790 / 31.170 / 15.015513025025650 / 36.9
DS-46-59046590 / 23.3945 / 37.270 / 15.018014528029050 / 36.9

Online Consultation